HomePrint Product Specs & Dimensions
Fulton VMP
Vertical Multi-Port Boiler
Specifications & Dimensions
Model | VMP-40 | VMP-49.5 | VMP-50 | VMP-60 | VMP-80 | VMP-100 | VMP-130 | VMP-150 |
---|---|---|---|---|---|---|---|---|
Specifications | ||||||||
Fuel Input - Natural Gas (CFH) | 1,594 | 1,974 | 1,993 | 2,392 | 3,188 | 3,986 | 5,181 | 5,979 |
Fuel Input - Propane (CFH) | 638 | 790 | 797 | 957 | 1,275 | 1,594 | 2,082 | 2,392 |
Fuel Input - #2 Oil (CFH) | 11.4 | 14.1 | 14.3 | 17.1 | 22.8 | 28.5 | 37.1 | 42.8 |
Steam Output (LB/HR) | 1,380 | 1,708 | 1,725 | 2,070 | 2,760 | 3,450 | 4,485 | 5,175 |
Output (MBH) | 1,339 | 1,658 | 1,674 | 2,009 | 2,678 | 3,348 | 4,352 | 5,022 |
Water Content - Operating (GAL) | 153 | 231 | 219 | 245 | 348 | 477 | 749 | 749 |
Dimensions | ||||||||
Height w/o Trim (IN) | 89.8 | 93.5 | 93.5 | 99.5 | 105.3 | 106.6 | 119 | 118 |
Height w/ Trim (IN) | 98.4 | 102.1 | 102.1 | 116.9 | 118.9 | 118.9 | 131.8 | 132.3 |
Width w/o Trim (IN) | 50.5 | 54.6 | 54.6 | 54.6 | 63.1 | 69 | 76.8 | 76.8 |
Width w/ Trim (IN) | 80.1 | 83.7 | 83.3 | 83.5 | 93.9 | 100.6 | 107.3 | 107.4 |
Depth (IN) | 103.7 | 105.4 | 105.4 | 100.8 | 115.6 | 120.3 | 131.8 | 133.3 |
Burner Pull (IN) | 110 | 115 | 115 | 125 | 130 | 132 | 145 | 145 |
Steam Outlet - 150 psi, trim (IN) | 3 | 3 | 3 | 3 | 4 | 4 | 4 | 4 |
Flue Outlet (IN) | 12 | 12 | 12 | 12 | 14 | 14 | 14 | 14 |
Weights | ||||||||
Shipping Weight (LBS) | 5,900 | 6,500 | 6,800 | 7,500 | 9,300 | 10,600 | 15,500 | 16,400 |
Operating Weight (LBS) | 7,175 | 8,424 | 8,631 | 9,545 | 12,208 | 14,577 | 21,749 | 22,649 |